Home ProductsHFO Fired Power Plant

Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV

China KANGWEI ENVIRONMENT ENERGY GROUP certification
China KANGWEI ENVIRONMENT ENERGY GROUP certification
We enjoy marine support from the WUXI KANGWEI since 2001, they have the appreciated experience in HFO fired diesel engine , HFO treatment system

—— Mr.Hua Hadi ,Haiphong shipyard

whenever the marine problem is related to the HFO treatment ,purification analysis of HFO power plant ,we rely on the support provided by the KANGWEI

—— Mr.Ali Hadi , Baghdad,Iraq

We trust the supported of them,They look at the heavy fuel oil system problem of power plant from different angles using different technologies.

—— Mr.MAHMOUD HADY,Saudi Arabia

I'm Online Chat Now

Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV

Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV
Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV

Large Image :  Containerized HFO Fired Power Plant , DO and LNG gas Power Plant 400V 11KV 33KV

Product Details:
Place of Origin: WUXI , CHINA
Brand Name: KANGWEI
Certification: ISO IEC
Model Number: According to the design and technical demand
Fuel: gas, light oil ,heavy fuel oil
Export Country: Indonesia;Sudan(10MW), mauritania, Sierra Leone
Payment & Shipping Terms:
Minimum Order Quantity: 1SET
Price: negotiated
Packaging Details: CONTAINER ,WOODEN CASE
Delivery Time: Negotiate
Payment Terms: T/T, L/C
Supply Ability: depend on the designing capacity
Detailed Product Description
Power Capacity: 1000-5000kw Each Engine Container: 40''
High Light:

heavy fuel oil power plant

,

hfo based power plant

Containerized HFO Fired Power Plant , Fuel Oil Power Plant 400V 11KV 33KV

 

 

1. Being in the decentralized energy sector benefit from the experience of  fuel treatment. Thereby many years of experience in power generation system integration and engineering applications guarantee customized solutions.

2. The kangwei container power station concept is an efficient and economic system designed for heavy fuel oil or gas fuelled applications.

 

For special fuel operation, the container represents an economic overall package consisting of a genset and auxiliary fuel processing, in two standardized container. Engineering and design are always adjusted to the requirements on special fuel operation.

 

The container is heat and noise insulated, and the slim, smooth wall design enables maximum utilisation of the interior space.

2. containerized diesel generator application as below

    Outdoor operation
    Semi-mobility (movability) possible
    Supplying important consumer at grid failure
    Power Plants
    rough environment power supply

 

3. Advantages of kangwei containerized power generation

  • Time saving installation
  • Flexibility in operation and location
  • Backup systems in combination and integration with renewable energy solutions
  • Operation with high quality components for low maintenance costs
  • Reduced transportation costs
  • Reduced installation and commissioning time
  • Factory tested system

G300 Generating Sets Main Specification

Model

1000GF1

1250GF3

1350GF4

1400GF4

Rated power, KW

1000

1250

1350

1400

Overload , KW

1100

1375

1485

1540

Rated voltage, V

400/415/440/3300/6300/10500/13800

Rated current , A

 

 

 

 

 

     

Frequency , Hz

50

60

50

60

50

60 50 60

Power factor

0.8 Lagging

Phase

3

Diesel engine

G6300ZD6

G6300ZD8

G8300ZD6

G6300ZD10

G8300ZD10

G8300ZD8 G8300ZD10 G8300ZD8

Rated power, KW

1103

1470

1471

1471

1765

2000 1765 2000

Rated rev, rpm

500

600

500

600

500

600 500 600

Alternator

3 phase alternator

voltage fluctuation rate%

<0.5

<0.5

Frequency fluctuation rate, %

<0.5

<0.5

Stable voltage regulating rate, %

±1.0

±1.0

Transient voltage regulating rate, %

+20, -15

+20, -15

Stable Frequency fluctuation rate, %

<3

<0.5

Transient frequency regulating rate, %

+12, -10

Stablizing time, voltage , S

<4

Stablizing time, frequency , S

<3

voltage regulating method

automatic and munual

Frequency regulating method

manual

starting method

compressed air

Lubricating method

pressue lubricating 

Cooking method

water cooling

coupling

flexible

Overdimension, mm

3880*2150*3180

8470*2360*3060

Weight, Kg

30000

35000

38000

G300  Generating Sets Main Specification
1500GF6 1600GF5 1800GF7 2000GF8
1500 1600 1800 2000
1650 1760 1980 2200
400/415/440/3300/6300/10500/13800
               
50 60 50 60 50 60 50 60
0.8 Lagging
3
G8300ZD10 G8300ZD8 G8300ZD10 G8300ZD8 G8300ZD8 G8300ZD8 G8300ZD12 G8300ZD8
1765 2000 1765 2000 2000 2000 2206 2000
500 600 500 600 600 600 600 600
3 phase alternator
<0.5
<0.5
±1.0
20, -15
<0.5
+20, -15
<5
<4
automatic and munual
manual
compressed air
pressue lubricating 
water cooling
flexible
8470*2360*3060
38000 42560

 

 

Remark

1. the generator voltage and frequency can be selected

2. rating for the generator set is based on the following standard conditions

air temperature :25℃

total barometric pressure 100kpa

charge air coolant temperature 25℃

relative humidity 30%

If test ambient conditions are not same as the standard ambient conditions, the power and fuel consumptions should be revised according to GB/T6072.1-2000

3. The generator set can operate under overload, intermittently for 1 hour every 12h, the fuel injection quantity is usualy locked in the rated power position

 

GN8320 Generating Sets Main Specification

Model

2400GF

2500GF

Rated power, KW

2400

2500

Overload , KW

2640

2750

Rated voltage, V

400

415

3300

6300

10500

400

415

3300

6300

10500

Rated current , A

4330

4174

525

275

165

4511

4348

547

172

286

Frequency , Hz

50

50

Power factor

0.8 Lagging

0.8 Lagging

Phase

3

3

Diesel engine

GN832000ZD

GN8320ZD

Rated power, KW

2648

2795

Rated rev, rpm

750

750

Alternator

3 phase alternator

voltage fluctuation rate%

±1.0

Frequency fluctuation rate, %

+12, -10

Stable voltage regulating rate, %

3

Transient voltage regulating rate, %

+12, -10

Stable Frequency fluctuation rate, %

4

 

Transient frequency regulating rate, %

5

Stabilizing time, voltage , S

+1

Stabilizing time, frequency , S

+12, -10

voltage regulating method

automatic and manual

Frequency regulating method

manual

starting method

compressed air

Lubricating method

pressure lubricating

Cooking method

water cooling

coupling

flexible

Overdimension, mm

8950*2570*6050

Weight, Kg

45000

 

 

Remark

 

1. the generator voltage and frequency can be selected

2. rating for the generator set is based on the following standard conditions

air temperature :25℃

total barometric pressure

charge air coolant temperature

relative humidity

If test ambient conditions are not same as the standard ambient conditions, the power and fuel consumptions should be revised according to GB/T6072.1-2000

3. The generator set can operate under overload, intermittently for 1 hour every 12h, the fuel injection quantity is usualy locked in the rated power position